City of Balmorhea
Anti-Data Center Policies
Balmorhea city requires shielded outdoor lights, limits their color temperature and brightness per acre, and gives existing fixtures five years to comply; these rules may add costs but do not bar data centers.
current law · City of BalmorheaRequires data centers in Balmorhea, like other properties, to follow outdoor-lighting rules limiting glare, brightness, and color temperature.Ordinance No. 2021-1 (Outdoor Lighting on Public and Private Property)
What this means
The ordinance would add lighting design and operating requirements to data center sites, including fully shielded fixtures, a 2,700 K color-temperature limit, and caps on outdoor lighting per acre (lighting standards). These could add cost or constrain brightly lit campuses, but the rules do not prevent data center construction or restrict their core operations, and existing fixtures get five years to comply (five-year compliance period).
People behind it
- City of Balmorhea Department of Planning and Community Development
Responsible for administering and enforcing the outdoor-lighting chapter.
Restrictions & requirementsHide restrictions & requirements11
Outdoor lighting on public and private property must comply with the ordinance. Fixtures installed, replaced, or repaired after its effective date must be fully shielded, and light trespass is prohibited except for limited governmental streetlight allowances. Fixtures must be fully shielded and all light trespass is prohibited.
Outdoor luminaires may not exceed a correlated color temperature of 2,700 Kelvin. The CCT shall not exceed 2700 Kelvins.
Total outdoor light output is capped at 50,000 lumens per net acre in any contiguous illuminated area on nonresidential property and 25,000 lumens per net acre on residential property. Government-owned streetlights serving public rights-of-way and outdoor recreation facilities are excluded. The nonresidential and residential lumen caps.
Outdoor signs face lighting and operating limits: externally illuminated signs must be lit from above with fully shielded fixtures that prevent spill beyond the sign, and all illuminated signs must turn off at 11 p.m. or within one hour after normal business hours end, whichever is later. Internal signs are limited to 50 nits and 50 square feet, with restrictions on background and light-colored areas. Sign lighting and curfew requirements.
Electronic message displays may not show a message for less than 30 seconds, may take no longer than 0.25 seconds to transition between messages, and may not use moving or flashing text or images. Electronic message display limits.
Unshielded outdoor illumination of buildings, landscaping, or signs is prohibited. Spotlights of 500 lumens or less are allowed only if shielded and aimed to keep light on the target. Landscape lighting restrictions.
String, rope, festoon, bistro, and similar lighting is limited to 50 lumens per individual lamp and 6,000 lumens total per installation, and must be rated at or below 2,700 Kelvin. String and similar lighting limits.
Searchlights are prohibited except for temporary emergency lighting; outdoor quartz lamps and mercury vapor lamps are prohibited; and laser or similar high-intensity lights may not be projected above the horizontal plane. Prohibited lighting fixtures.
Building permit applications that include installation of outdoor lighting must provide evidence of compliance on a form supplied by the Department of Planning and Community Development. Outdoor-lighting compliance evidence is required.
Existing noncompliant outdoor fixtures had to be brought into compliance within five years of the ordinance date. Existing fixtures must comply within five years.
Violations are civil infractions enforceable under the municipal code’s code-enforcement chapter. Violations constitute a civil infraction.
Benefits & exceptionsHide benefits & exceptions2
The Director may exempt outdoor lighting for temporary or periodic events, including nighttime construction, allowing approved temporary construction lighting without applying the ordinance’s usual requirements. Outdoor lighting approved by the Director for temporary or periodic events.
Existing noncompliant outdoor fixtures have five years from the ordinance’s enactment to be brought into compliance, giving existing facilities time before required upgrades. Existing noncompliant outdoor light fixtures.