Upper Uwchlan Township

Neutral Data Center Policies

Upper Uwchlan Township allows data centers in designated districts through special permit or conditional-use review, providing a defined approval path but adding time and uncertainty.

Incentives

Financial Incentive

Financial incentives not assessed from full ordinance text in this tracker import; an empty list is not a confirmed finding that no incentive exists.

current law · Upper Uwchlan Township
Creates a data-center-specific ordinance in Upper Uwchlan Township, but the provided text does not show what it requires or restricts.Ordinance No. 2026-03 — Data Center Ordinance (including Upper Uwchlan Township Zoning Ordinance § 200-72.4 and § 200-44(13))
current law · Upper Uwchlan Township
The current rules are in Ordinance 2026-03, which the Board of Supervisors adopted on August 17, 2026.Upper Uwchlan Township, Chester County — data-center ordinance (No. 2026-03)

What this means

The measure provides a route for data centers through a special permit or conditional-use review in designated districts. That offers legal certainty, but the extra approval step can add time and uncertainty.

Restrictions & requirementsHide restrictions & requirements25
  • LI Limited Industrial district only, § 200-44.B(13)

  • Conditional use by Board of Supervisors; approval lapses in 6 months, § 200-116.H.

  • Section 200-72.4.B sets data centers and data center accessory uses back 1,000 feet from any lot developed with a sensitive receptor, and Section 200-72.4.D defines those accessory uses to include ground level and rooftop mechanical equipment.

  • 35 ft, rooftop equipment not limited, § 200-72.4.C

  • 55 dBA day, 45 dBA night at residential, § 200-72.4.G(9) Table 2

  • Section 200-72.4.G(9), Table 6, makes an increase of more than 3 dBA above the documented baseline ambient level a violation, measured with an ANSI Type 1 or Type 2 meter (Table 5), but the baseline is not defined as L90 and no floor is set below which the cap does not apply.

  • 70 dBC day, 60 dBC night, Table 3

  • Pre-construction and post-construction studies, § 200-72.4.G(1), (3)

  • 65 VdB and PPV limits with study, § 200-72.4.G(3)(f)

  • Public water required, no groundwater for cooling; no well study, § 200-72.4.H

  • Air-cooled or closed-loop required; evaporative not named, § 200-72.4.H(5)

  • Usage estimates and drought plan; no cap or reporting, § 200-72.4.H

  • Tier 4 generators with annual testing reports, § 200-72.4.F(7)

  • Electronic waste plan; refrigerants in decommissioning, § 200-72.4.M, N.

  • Utility interconnection documentation; no electrical inspection, § 200-72.4.F(6)

  • Energy usage plan; renewables encouraged only, § 200-72.4.F

  • Substations side or rear and screened; lines 34.5 kV or less buried, § 200-72.4.J

  • Mechanical equipment screened on all sides, § 200-72.4.D

  • Elevations and renderings required, § 200-72.4.E

  • Plan reviewed by fire department, radio coverage, 24-hour signage; no annual update, § 200-72.4.K

  • Annual fire safety inspections, § 200-72.4.K(1)(e)

  • Construction plan for vehicle times and locations; no bond, § 200-72.4.L

  • Plan and closure notice; security optional, 18 months, § 200-72.4.N

  • One post-construction noise study, § 200-72.4.G(3)

  • Generator testing website only

Benefits & exceptionsHide benefits & exceptions1
  • Approval pathway: Conditional use in the LI Limited Industrial district

Sources

Thank you to the Pennsylvania Data Center Ordinance Tracker for providing proposed local ordinance data for PA. Citation: padatacenterordinances.org, accessed November 3, 2026.Cookie preferences · Report missing data