Union Township
Anti-Data Center Policies
Union township’s listed measure limits noise, requires sound testing, sets setbacks from homes and other protected places, and restricts building height; data centers may still be approved, but compliance can add costs.
Incentives
Financial Incentive
Financial incentives not assessed from full ordinance text in this tracker import; an empty list is not a confirmed finding that no incentive exists.
current law · Union CityBorough Council adopted Ordinance No. 1188 on August 11, 2026, the same day as its public hearing, amending Zoning Ordinance No. 1118.Union City, Erie County — data-center ordinance (No. 1188)
What this means
The measure imposes noise limits and sound testing, setbacks from homes or other protected places and building-height limits. Data centers can still be approved, but these obligations meaningfully increase construction, compliance or review costs.
Restrictions & requirementsHide restrictions & requirements25
Environmental Impact Assessment including riparian buffers and wetlands, and floodplain exclusion, § 4.B and J
67 dBA day and 57 dBA night and weekend at the property line, 57 dBA at residential boundaries, § 4.C.1 and C.4
Section 4.C.1 requires preliminary, interim, and as-built studies using ANSI S1.4 meters and generally accepted methodology.
Vibration study showing nothing perceptible beyond the property line, § 4.C.2.
Water Utilization Report and provider capacity certification; wells not barred, § 4.F
Cooling system type and efficiency disclosed, § 4.F.1
Total daily intake volume disclosed; no cap, reporting, or drought plan, § 4.F.1
Section 4.G requires the applicant to demonstrate that domestic, cooling, and industrial wastewater disposal has been provided and approved by the Union City Municipal Authority or DEP.
Compliance with borough stormwater ordinances required, § 4.F.1
Backup generators must meet EPA Tier 4 with annual testing reports, § 4.D
Thermal Impact Mitigation Plan including waste heat reuse, § 4.I.
Electronic Waste Plan for servers, hazardous materials, and batteries, § 4.H.
Provider certification of capacity; no third-party electrical inspection, § 4.E.3.
Energy Management Plan; renewable energy is a good-faith effort only, § 4.E.1 to E.2
On-site generation is a separate use with separate permits; no separate setbacks, § 4.E.4
Accessory substations screened or enclosed near roads and homes, § 4.R.1
Known rate impacts must be provided, § 4.E.3
100-ft buffer along property lines next to residential uses or zoning, § 4.P.2.
Equipment within 75 ft enclosed or screened, rooftop screened on four sides; no height standard, § 4.R
Emergency Response Plan accepted by the fire department with 24-hour contact signage; no annual updates, § 4.V
First responders must receive system-specific training, § 4.V
Annual fire safety inspections, § 4.V
Section 4.B.2 requires a traffic study of the impact of data center traffic on the surrounding area, neighborhoods, and roads.
One as-built sound study after opening; annual reports cover emissions, not noise, water, or power, § 4.C.1 and D.2
Section 4.X requires a $5,000 escrow, replenished on request, for Borough engineering and legal fees in the application and permitting process.
Benefits & exceptionsHide benefits & exceptions1
Approval pathway: Special exception in the Industrial District
Sources