Anti-Data Center Policies
Mayfield borough’s enacted ordinance limits noise and building height, requires sound testing and setbacks from homes and other protected places, and adds costs; data centers can still be approved.
Incentives
Financial Incentive
Financial incentives not assessed from full ordinance text in this tracker import; an empty list is not a confirmed finding that no incentive exists.
current law · Mayfield BoroughBorough Council adopted the rules as Ordinance 2025-14 on December 10, 2025, and its October 14, 2026 agenda listed a public hearing on the new NorLACK zoning ordinance, which the county reported would not permit data centers, together with a motion to readvertise that ordinance with amendments before adoption.Mayfield Borough, Lackawanna County — data-center ordinance (No. 2025-14)
What this means
The measure imposes noise limits and sound testing, setbacks from homes or other protected places and building-height limits. Data centers can still be approved, but these obligations meaningfully increase construction, compliance or review costs.
Restrictions & requirementsHide restrictions & requirements15
67 dBA day and 57 dBA night at the property line, § 6.500.F.1
Section 6.500.F.1 of Ordinance 2025-14 requires preliminary (conditional use), interim (building permit), and as-built sound studies using ANSI S1.4 meters and generally accepted methodology, but the limits apply during normal operations and the as-built study is not required at full operating load.
Vibration study showing none perceptible past the property line, § 6.500.F.3.
Water feasibility study when nonpublic water is used; no bar on wells for cooling, § 6.500.G.2
Projected water demand and uses disclosed, § 6.500.G.2
Section 6.500.G.4 requires the applicant to demonstrate that adequate disposal of domestic, cooling, and industrial wastewater has been provided and approved by the Sewage Enforcement Officer or DEP.
Utility certification and interconnection agreement; no electrical inspection, § 6.500.H.1 and H.3.
Generation for normal operations is a separate use with its own approval, § 6.500.H.2.
25-ft planted buffer, § 6.500.D
Equipment within 300 ft enclosed or screened, § 6.500.E.1
Emergency plan accepted by the fire department; no annual update, radio, or 24-hour contacts, § 6.500.I.1
Plan must ensure responder training; no funding, § 6.500.I.1.d
Annual fire safety inspections, § 6.500.I.1.e
One as-built sound study after opening, § 6.500.F.1.c
Failed as-built study is a violation; no specific penalties, § 6.500.F.1.c
Benefits & exceptionsHide benefits & exceptions1
Approval pathway: Conditional use in the C-2 Commercial District
Sources