Manchester Township

Anti-Data Center Policies

Manchester Township’s enacted ordinance limits data-center noise and building height, requires sound testing and setbacks from homes and other protected places, and adds costs; approval remains possible.

Incentives

Financial Incentive

Financial incentives not assessed from full ordinance text in this tracker import; an empty list is not a confirmed finding that no incentive exists.

current law · Manchester Township
The current rules are in Ordinance 2026-04, which the Board of Supervisors adopted by a 5 to 0 vote on June 9, 2026, following a public hearing held that evening.Manchester Township, York County — data-center ordinance (No. 2026-04)

What this means

The measure imposes noise limits and sound testing, setbacks from homes or other protected places and building-height limits. Data centers can still be approved, but these obligations meaningfully increase construction, compliance or review costs.

Restrictions & requirementsHide restrictions & requirements23
  • Conditional use; no approval expiration, § 27-1301.A

  • Agricultural districts protected only by the 400-ft setback, § 27-1301.B.4

  • Single 67 dBA limit at the property line, § 27-1301.E.1

  • Sound study by an acoustical expert plus an as-built study six months after occupancy, § 27-1301.E.1

  • Generators must be fully enclosed; no testing hours or hours cap, § 27-1301.E.2

  • Vibration study showing none perceptible beyond the property line, § 27-1301.E.1.b.

  • Water feasibility study for nonpublic sources; no bar on wells for cooling, § 27-1301.G.2

  • Projected water demand and use by purpose, including cooling, disclosed, § 27-1301.G.2

  • Cooling and industrial wastewater disposal must be approved by the sewage officer or DEP, § 27-1301.G.2.k

  • Hazardous materials removed and disposed of under law at decommissioning, § 27-1301.K.4.e

  • Utility certification of capacity and service; no electrical inspection, § 27-1301.H.1.

  • Substations are accessory uses, and power equipment within 300 ft of roads or homes must be enclosed or screened, § 27-105 and § 27-1301.D.1

  • Known electric rate impacts must be noted; no cost assignment, § 27-1301.H.1

  • 100-ft planted buffer next to residential districts, sensitive receptors, homes, and roads, § 27-1301.C.1.

  • Cutoff luminaires with 0.1 footcandle limit at homes and 3000K cap, § 27-1301.F

  • Equipment within 300 ft of roads, residential districts, or sensitive receptors enclosed or screened; 8-ft fence cap, § 27-1301.D

  • Emergency plan accepted by the fire department and 24-hour contact signage; no annual update or radio coverage, § 27-1301.I.1 and I.4

  • Plan must ensure first responders are trained; no funding, § 27-1301.I.1.d

  • Annual fire safety inspections; no electrical inspection, § 27-1301.I.1.e

  • Security of 110% of cost, but no closure notice and no removal deadline after 24 months of inactivity, § 27-1301.K

  • Security adjusted every 5 years; no first-year update, § 27-1301.K.3.c

  • One as-built sound study, with more only if the township requires, § 27-1301.E.1.a

  • Noise found by the as-built study is a violation; no specific penalty, § 27-1301.E.1.a

Benefits & exceptionsHide benefits & exceptions1
  • Approval pathway: Conditional use in the Industrial and Heavy Industrial Districts

Sources

Thank you to the Pennsylvania Data Center Ordinance Tracker for providing proposed local ordinance data for PA. Citation: padatacenterordinances.org, accessed November 3, 2026.Cookie preferences · Report missing data