Briar Creek Township

Neutral Data Center Policies

Briar Creek Township’s enacted ordinance adds site and approval requirements for data centers, creating a modest compliance burden without clearly blocking otherwise eligible projects.

Incentives

Financial Incentive

Financial incentives not assessed from full ordinance text in this tracker import; an empty list is not a confirmed finding that no incentive exists.

current law · Briar Creek Township
The standards are in Section 456 of the Briar Creek Township Zoning Ordinance of 2026, Ordinance 1 of 2026, which the Supervisors enacted on June 1, 2026.Briar Creek Township, Columbia County — data-center ordinance (No. 1 of 2026)

What this means

The measure imposes extra site and approval requirements. These add a modest compliance burden without clearly preventing otherwise eligible projects.

Restrictions & requirementsHide restrictions & requirements26
  • Conditional use before the Supervisors; expiration of approval not confirmed

  • 200 ft minimum setback on all sides, Section 456.1.e

  • 40 ft overlay height limit and generators may not sit above the roof line; no rooftop equipment height cap, Sections 311 and 456.1.f

  • Environmental buffers review and impact assessment of wetlands, riparian corridors, and recharge zones, Sections 456.1.a and 456.3

  • Single limit of 50 dBA at the property line, Section 456.1.f

  • Noise protocol with projected day and night levels required with the full impact assessment, Section 456.3.a.iv

  • Generator testing only on weekdays from 9 a.m. to 5 p.m.; no hours cap, Section 456.1.f

  • Vibration isolation required for generators and mechanical systems, Sections 456.1.f and 456.3.a.iv

  • Stamped water use plan and hydrogeological study where wells or recharge areas are involved; no bar on wells for cooling, Sections 456.1.g and 456.3.a.iii

  • Closed-loop, hybrid, or reclaimed-water cooling required and open-loop prohibited, but hybrid systems are allowed, Section 456.1.g

  • Daily and peak water use must be disclosed, Sections 456.1.a and 456.3.a.ii

  • Heat island contributions must be analyzed, Section 456.3.a.v

  • Utility coordination plan confirming substation capacity and transformer size; no third-party electrical inspection, Section 456.3.a.ii

  • Electrical demand and load documentation required, Section 456.3.a.ii

  • Required utility upgrades must be identified, Section 456.3.a.ii

  • Section 456.1.e requires a 200 ft minimum setback and a 200 ft minimum buffer of native evergreens, berms, opaque fencing, and a gravel firebreak, with effective layering for noise and visual impact, but it does not require replacement of dead or diseased plants.

  • Long facades must include articulation, step-backs, or landscaping, Section 456.1.e

  • Opaque fencing, acoustic shielding, and baffled generator enclosures required, Sections 456.1.e and 456.1.f

  • Visual impact analysis of massing and sightlines; no renderings required, Section 456.3.a.v

  • Fire protection and emergency operations plan with site maps given to emergency services, Section 456.3.a.i

  • Applicant must show its contribution to local fire department equipment and offset emergency service needs, Sections 456.3.a.i and 456.3.a.vii.

  • Site maps must show fuel and battery locations; no storage setbacks or spill containment, Section 456.3.a.i

  • Annual fire walkthrough required, Section 456.1.d

  • Traffic analysis required only for projects that trigger the full impact assessment, Sections 456.2 and 456.3.a.vii

  • Two ingress and egress points required; no arterial or collector road requirement, Section 456.1.c

  • Removal and restoration within 180 days of notice with bonding; no 110% amount, Section 456.1.j

Benefits & exceptionsHide benefits & exceptions1
  • Approval pathway: Conditional use in the Data Center and Technology Overlay, and for minor data centers in the Industrial District

Sources

Thank you to the Pennsylvania Data Center Ordinance Tracker for providing proposed local ordinance data for PA. Citation: padatacenterordinances.org, accessed November 3, 2026.Cookie preferences · Report missing data